P: Ai besonh de testar un cable de 220 kV, de 8 km de long. Quina nòta SR ai besonh?
A: Procediment de dimensionament en 7 estapas: determinar los requisits de tèst → calcular C → estimar L → calcular f_res → verificar las nòtas → iterar → finalizar.
Pas-per-pas - 220 cable kV, 8 km:
1. IEC 60840: V_test=2.0 × 127 kV=254 kV. Durada 60 min.
2. C ≈ 8 km × 0.2 μF/km=1.6 μF.
3. Consideratz los reactors 3× 100 kV/2 A en parallèl: L=26.7 H, f=24.4 Hz.
4. Corrent a 254 kV: I=V × 2πf × C=6.9 A. Mas 3×2A → 6A total → PAS OK.
5. Mesa a jorn a 3× 100 kV/4 A de reactors: total I=12 A → OK. P_en=254×6.9/35=50 kW.
6. Pes total: 3×450 kg + 200 + 150 + 100=~1,800 kg.
Resumit de dimensionament per d'escenaris comuns:
|
Scenari |
V_test (kV) |
C (μF) |
f (Hz) |
Sistèma recomandat |
|
Cable de 33 kV, 3 km |
48 |
0.6 |
45 |
60 kV/2A ×1, 5 kW |
|
Cable de 110 kV, 5 km |
160 |
1.0 |
24 |
200 kV/4A ×2, 20 kW |
|
Cable de 220 kV, 8 km |
254 |
1.6 |
24 |
300 kV/4A ×3, 50 kW |
|
Cable de 400 kV, 5 km |
330 |
1.0 |
48 |
400 kV/2A ×2, 25 kW |
|
SIG 245 kV, 10 baias |
230 |
0.05 |
80 |
300 kV/1A ×2, 5 kW |
|
Generador 100 MVA |
28 |
2.5 |
45 |
30 kV/5A, 10 kW |
Rapèls critics :
• +20% de marge sus la tension nominal del reactor. +30% marge sus la corrent nominal.
• Se P_in > 100 kW, consideratz los tèsts seccionals (permés per la màger part de las nòrmas).
• Lo Q real pòt èsser inferior a l'estimat - la planificacion conservatritz evita los fracasses de camp.